Troubleshooting Powermanager
The following section describes how to handle common import error conditions.
Message | Situation | Do the following... |
| The selected CSV import file cannot be loaded by the Desigo CC importer. | Verify that the CSV file uses a comma (,) character as separator. Any other character will result in an invalid file format. Refer the sample CSV file provided. |
| The configuration file selected for the import is invalid. | In the Import tab, click Analysis Log and check the pre-import log. Try again using another configuration file. |
| The default Tomcat memory of 2500 MB is insufficient to generate cache for a system with more than 500 managed meters configured. In such situations you must set the Tomcat memory to a higher limit, for example, 6000 MB. | From the Services dialogbox, stop the Tomcat service. Navigate to the following path: Select the Java tab and navigate to the Maximum memory pool field. Set the memory to higher value and click Apply and OK. Now re-start the Tomcat service and try again. |
| This is due to the cache of the web browser content of the charts which has not loaded | Close powermanager and powermanager SMC(do not stop the applications, just close them) Delete |
| Tomcat is not installed or has stopped | 1)Check if Tomcat is installed. If not installed, install and place the report files and start Apache Tomcat from Services.msc 2)If already installed,start Apache Tomcat from Services.msc |
| WSI has stopped working | Start WSI from Console |
| The password has been changed | Enter the correct credentials to edit the selected report definitions. |
| There is no sufficient C drive space and memory and many devices are connected. | Increase system C drive space and memory |
| Too many measurement points, connected to Powermanager, are archived | Unselect some of the archived measurement points and continue |
| When create report definition is clicked, a blank page is displayed. | Exit the application and re login |
| Switch between report definition and application viewer | Click on the report and click on application viewer |
| Occurs when the object models in the libraries are corrupt | Create the new project through template. |
| The device is flickering and there is a communication error. Hence, the data is not polled. | Check the device communication and try connecting again |
| The device is flickering and there is a communication error. Hence, the data is not polled. | Contact the system administrator to grant extended permissions. |
| This could happen if the WCCOAGmsCoHoMngr in the WinCCOA console would have stopped | Check if it is stopped and try restarting the control, then try logging in to application |
| When GMS_Licensing is stopped, this error is displayed in the splash screen of the application | Try restarting GMS_Licensing.ctc manager in WinCCOA console and logging in to application |
| Powermanager 4.1 requires powershell 5.1 or higher for all the steps to be completed successfully. | Install powershell 5.1 from the microsoft website. |
| There is a license in the SYSTEMDRIVE\AX NF ZZ folder | Delete the license in case of trail license or transfer the license |
| If any version of Visual C++ redistributable higher than 14.0.24213 is found in the PC. | Uninstall the Visual C++ redistributable higher than 14.0.213, note that few versions will not have an uninstall option in control panel. |
| In the entry fields of the platform: You can use UTF-8 characters and 7-bit ASCII characters in the file or project names and paths. However, blank spaces and special characters including \\, :, /, \, :, ,, =, ^, &, *, ?, “, <, >, |, @, [, ], {, }, $, !, %, ., (, ), ‘ “ ‘, \t are not permitted. You must not use any characters other than A through Z, numbers 0 through 9, and a hyphen (-). Forward and backward slashes (\ and /) can only be used to separate the names of directories. According to WinCC OA 3.16 Help: Umalaut (“ä”, “ö”, “ü”) – cause problems during online backup. | Change the project name and retry. |
| JDK 11.0.2 is neccasary for installation of few components of powermanager , hence this warning appears. | Download Open JDK 11.0.2 from the below link Extract the contents and place the jdk-11.0.2 folder in C:\Siemens\Java\ |
| The website name must be a unique name. You cannot have sites in IIS with the same name. Following special characters are not permitted in the website name: \\’, ‘/’, ‘?’, ‘;’, ‘:’, ‘@’, ‘&’, ‘=’, ‘+’, ‘$’, ‘,’, ‘|’, ‘ “ ‘, ‘<’, ‘>’. | Change the website name and retry. |
| To access WSI from a remote machine, WEB server communication has to be secure. | Both the root and host certificates have to be created from server and same to be imported in Client. |
| You in to the application and the courtesy/demo mode appears in summary bar | Check if customer has proper license in LMU(License management utility) Check the license platform version Check if license related services are running properly Make sure user has purchased enough number of licenses |
| Issue may occur in virtual box machine when license in pointed from host machine.
You get this error when you try to open winccoa console. But you will able to login to powermanager and to switch to engineering mode | Restart the following licensing services and restart WinCCOA: FlexNet Licensing services Automation License manager service BT Licensing server |
| Issue may occur in virtual box machine when license in pointed from host machine | Add two programs(LMS Imgrd & LMS siembt) in firewall exception; make sure test connection is successful from VM’s LMU Also, make sure that ports are open from firewall to communicate to host machine |
| Issue may happen when SQL server service stops | Make sure SQL Server(GMS_HDB_Express) service runs properly |
| Website and its application is not configured properly OR Application is running for few days and kept idle OR The dashboard does not load after right dashboard configuration | Make sure website is up and running in SMC Make sure that proper configuration is done for websites in powermanager Exit the application and login again |
| This can happen if the converted unit from the device is changed and user moves to default tab in operating mode | Click on graphics page and press Alt+Ctrl+Shift+O from keyboard Click on – Clear symbol cache in the new window Navigate to graphics node in system tree Navigate back to device node |
| This may happen if project is not running properly or closed mode service is not running | Make sure that project and Siemens GMS closed mode service runs properly |
| This may appear when you try to open powermanager as client in browser | Make sure that certificates are configured properly in client machine |
| This may happen if powermanager is installed as client but there is a time difference between server and client | Synchronize the system time of client and server |
| Right communication parameters should be used when PAC4200 device is created and started. Also, this could happen when the alarms are not loaded in the alarm bar of powermanager application | Check if the alarms are present in the PAC4200 device HMI If they are present in device and not listed in the application, stop the device and start it again |
| Right communication parameters should be used when PAC4200 device is created and started. This may happen if the High and low alarm counts (in alarm bar of powermanager application) are not same as compared to alarm count in device HMI | Check if the alarms are present in the PAC4200 device HMI Count the number of High and Low alarms in the device HMI If there is a mismatch in powermanager application, stop the device and start it again |
| Right communication parameters should be used when PAC4200 device is created and started. This may happen if there is a mismatch in the alarm configuration like alarm classes or alarm type (High or Low) in alarm bar of powermanager application when compared to the device HMI | Check if the alarm class in the device HMI is same as per the configuration Check if the alarm type in the device HMI is same as per the configuration If there is a mismatch in powermanager application, stop the device and start it again |